CA1-B0-34-615-121-D [Carling Technologies]
CKTBKR;型号: | CA1-B0-34-615-121-D |
厂家: | Carling Technologies |
描述: | CKTBKR 电路保护 |
文件: | 总28页 (文件大小:4211K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
C-
riesSeries
C-Se
CIRCUIT BREAKER
The C-Series hydraulic-magnetic circuit breakers are ideal for applications that require higher amperage and
voltage handling capability in a smaller package. They are available in 1-6 poles, 0.02-100amps, UL Recognized
up to 480VAC or 150VDC, UL489 Listed up to 240VAC or 125VDC, with choice of time delays, terminal
options, actuator styles and colors. The C-Series employs a unique arc chute design which allows for higher
interrupting capacities of up to 10,000 amps. New thermoset glass filled polyester half shell construction
provides for increased mechanical and electrical strength. The wiping contacts, mechanical linkage with two
step actuaction, clean contacts providing high, positive contact pressure and longer contact life. Available with
American Standard or Metric Threaded Stud terminals , or Saddle Clamp screw terminals. The optional mid-trip
handle style actuator allows a visual indication of electrical overload with or without alarm feature.
Eco-Friendly
Resources:
Download 3D CAD Files
IGS
STP
Product Highlights:
Extensive list of Agency Approvals
Typical Applications:
Marine
Available with Standard or Metric Stud terminals, Telecom/Datacom
or Saddle Clamp screw terminals
Optional mid-trip handle style actuator
Military
Renewable Energy
Unique arc chute design which allows for higher
Generators & Welders
interrupting capacities of up to 10,000 amps
Exclusive Rockerguard and Push-To-Reset bezel
Available with new solid color and two-color Visi-
rocker® actuators
New thermoset glass filled polyester half shell
construction
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Email: sales@carlingtech.com
Application Support: team2@carlingtech.com
Phone: 860.793.9281 Fax: 860.793.9231
www.carlingtech.com
|
2
C-Series – General Specifications
Electrical Tables
Table A: Lists UL Recognized & CSA Accepted configurations and performance capabilities as a Component Supplementary
Protector
C-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTORS
SHORT CIRCUIT CAPACITY (AMPS)
VOLTAGE
CURRENT RATING
APPLICATION CODES
UL/CSA
CIRCUIT
CONFIGURATION
NOTES
WITH BACKUP
FUSE 1
MAX.
RATING
FULL LOAD
AMPS
GENERAL
PURPOSE AMPS
WITHOUT BACKUP
FREQUENCY PHASE
UL
CSA
FUSE
32
48
65
DC
DC
DC
---
---
---
0.02 - 100
110 - 150
0.02 - 70
---
---
---
---
---
---
---
---
---
---
5000
5000
5000
5000
7500
7500
10,000
10,000
5000
5000
5000
3000
5000
5000
5000
3500
3000
1000
5000
3500
5000
---
TC1, OL1, U2
TC1, OL1, U2
TC1, OL1, U2
TC1, OL1, U2
---
---
TC1,2, OL1,U1 TC1,2, OL1,U1
TC1,2, OL0,U1 TC1,2, OL0,U1
TC1,2, OL1,U1 TC1,2, OL1,U1
TC1,2, OL0,U1 TC1,2, OL0,U1
TC1,2, OL1,U1 TC1,2, OL1,U1
TC1,2, OL0,U1 TC1,2, OL0,U1
71 -100
0.02 - 70
---
---
80
80
DC
DC
---
---
71 -100
0.02 - 70
---
---
Must Have Agency Code "L"
Must Have Agency Code "L"
71 -100
125
125 / 250
250
DC
DC
DC
---
---
---
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 100
0.02 - 100
---
---
TC1,2,OL1,U1
TC1,2,OL1,U1
TC1,2,OL1,U1
TC1, OL1, U2
TC1,2,OL1,U1
TC1, OL0, U3
TC1, OL0, U3
TC1, OL1, U2
TC1,2,OL1,U1
TC1,2,OL1,U1
TC1,2,OL1,U2
TC1, OL1, U2
TC1,2,OL1,U1
TC1,2,OL1,C1
TC1, OL0, U2
TC1,2,OL1,C1
TC1,2,OL0,U1
TC1,2,OL1,C1
TC1,2,OL1,C1
TC1,2,OL0,C1
TC1,2,OL1,C1
TC1,2,OL0,C1
TC1,2,OL1,U1
TC1,2,OL1,U1
TC1,2,OL1,U1
TC1, OL1, U2
TC1,2,OL1,U1
---
Must Have Agency Code "L"
---
Must Have Agency Code "L"
---
Must Have Agency Code "L". 2 Pole Break Required for 250 Volts
Per Pole Rating
---
---
---
125
50 / 60
1
---
Must Have Agency Code "L"
150
150
DC
DC
---
---
80 - 100
---
Must Have Agency Code "L"
---
101 - 175
---
---
Must Have Agency Code "L" Parallel Pole
SERIES
0.02 - 100
0.02 - 50
51 - 100
0.02 - 100
0.02 - 50
0.02 - 100
51 - 70
---
---
---
TC1, OL1, U2
TC1,2,OL1,U1
TC1,2,OL1,U1
TC1,2,OL1,U2
TC1, OL1, U2
TC1,2,OL1,U1
TC1,2,OL1,C1
TC1, OL0, U2
TC1,2,OL1,C1
TC1,2,OL0,U1
TC1,2,OL1,C1
TC1,2,OL1,C1
TC1,2,OL0,C1
TC1,2,OL1,C1
TC1,2,OL0,C1
---
---
2 or 3 poles breaking single phase
2 or 3 poles breaking single phase
2 or 3 poles breaking single phase, "L" Agency Code
Per Pole Rating
125 / 250
50 / 60
1
---
---
---
---
---
---
1
3
---
---
Must Have Agency Code "L"
---
5000
---
250
50 / 60
0.02 - 100
3000
---
0.02 - 70
---
---
0.02 - 90
---
5000
---
3 poles breaking 3 phase
5000
---
Must Have Agency Code "L"
277
50 / 60
50 / 60
1
3
0.02 - 50
0.02 - 30
---
5000
5000
5000
5000
5000
---
---
---
3 poles breaking 3 phase
2 poles breaking 1 phase
480 / 277
31 - 50
---
---
0.02 - 30
---
---
480
50 / 60
1
31 - 50
---
---
80
DC
---
1
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 30
---
7500
3000
3500
3000
3500
3000
---
TC1,2, OL1,U1 TC1,2, OL1,U1
125
50 / 60
---
---
TC1, OL1, U2
TC1, OL1, U2
TC1,2,OL1,U1
TC1, OL1, U2
TC1, OL0, U2
TC1,2,OL1,C1
TC1,2,OL1,C1
TC1, OL1, U2
TC1, OL1, U2
TC1,2,OL1,U1
TC1, OL1, U2
TC1, OL0, U2
TC1,2,OL1,C1
TC1,2,OL1,C1
Per Pole Rating
---
---
2 or 3 poles breaking single phase
2 or 3 poles breaking single phase
125 / 250
50 / 60
1
1
3
---
---
DUAL COIL
---
---
250
50 / 60
---
---
Per Pole Rating
---
5000
5000
---
277
80
50 / 60
DC
1
---
1
---
---
3 poles breaking 3 phase
---
7500
---
TC1,2, OL1,U1 TC1,2, OL1,U1
277
250
50 / 60
50 / 60
---
5000
5000
5000
5000
5000
5000
---
TC1,2,OL1,C1
TC1,2,OL1,C1
TC1,2,OL1,C1
TC1,2,OL0,C1
TC1,2,OL1,C1
TC1,2,OL0,C1
TC1,2,OL1,C1
TC1,2,OL1,C1
TC1,2,OL1,C1
TC1,2,OL0,C1
TC1,2,OL1,C1
TC1,2,OL0,C1
3
---
---
3 poles breaking 3 phase
3 poles breaking 3 phase
SHUNT
RELAY
---
---
480 / 277
480
50 / 60
50 / 60
3
1
31 - 50
---
---
0.02 - 30
---
---
2 poles breaking 1 phase
31 - 50
---
---
80
DC
---
1
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 70
---
7500
---
TC1,2, OL1,U1 TC1,2, OL1,U1
277
250
50 / 60
50 / 60
---
5000
5000
---
TC1,2,OL1,C1
TC1,2,OL1,C1
3
---
---
TC1,2,OL1,C1
TC1,2,OL1,C1
3 poles breaking 3 phase
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
65
80
DC
DC
---
---
71 -100
---
---
---
0.02 - 70
---
---
---
71 -100
---
---
---
125
50 / 60
50 / 60
1
1
1
3
1
0.02 - 100
0.02 - 100
0.02 - 100
0.02 - 70
0.02 - 50
0.02 - 30
---
---
---
SWITCH ONLY
125 / 250
---
---
---
2 or 3 poles breaking single phase
3 poles breaking 3 phase
---
---
---
250
277
50 / 60
50 / 60
50 / 60
---
---
---
---
---
---
---
---
---
480 / 277
3
31 - 50
---
---
Notes for Table A:
1
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less rating and
not to exceed 175 for 51 through 100 Amp rating
*Manufacturer reserves the right to change product specification without prior notice.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
C-Series – General Specifications
3
Electrical Tables
Table B: Lists UL Recognized and CSA Accepted configurations and performance capabilities as a Manual Motor Controller.
RELAY
Notes for Table B:
1
UL recognized and CSA Accepted at 480V refers to 3 & 4 pole versions used in a 3Ø, wye connected circuit or 2-pole version connected with 2 poles breaking. 1Ø and backed up with
series fusing as stated above in note 1.
*Series, Shunt and Relay Trip - Voltage Coil Construction not current coils
Table C: Lists UL Recognized, CSA Accepted , VDE and TUV Certified configurations and performance capabilities as a
Component Supplementary Protector.
Notes for Table C:
1
2
General Purpose ratings for UL/CSA only.
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less rating and
not to exceed 175 for 51 through 100 Amp rating.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
4
C-Series – General Specifications
Electrical Tables
Table D: Lists UL Listed (489), CSA Certified (C22.2 No. 5.1-M) configuration and performance capabilities as a Molded Case
Circuit Breaker.
C SERIES TABLE D : UL489 LISTED BRANCH CIRCUIT BREAKERS
INTERRUPTING
CURRENT
RATING
VOLTAGE
FREQUENCY
DC
CAPACITY
(AMPS)
CIRCUIT
CONFIGURATION
CONSTRUCTION NOTES
MAX.
FULL LOAD
AMPS
WITHOUT
BACKUP FUSE
PHASE
---
RATING
50,0001
10,000
Limited to 2 Poles Max from 71 - 100 Amps.
80
0.10 - 100
Limited to 2 Poles Max from 71 - 100 Amps.
125
DC
DC
---
---
0.10 - 100
0.10 - 50
0.10 - 50
51 - 70
5,000
5,000
1 - 3 Poles
125 / 250
1 or 2 Poles (2 Poles Required for 250 Volts)
10,000
5,000
1 - 3 Poles
120
50 / 60
50 / 60
1
1
SERIES
1 - 3 Poles
0.10 - 50
5,000
2 or 3 Poles. 1 Pole of a 3 Pole Unit is Neutral
120 / 240
10000 1
5,000
2 or 3 Poles. 1 Pole of a 3 Pole Unit is Neutral
0.10 - 50
0.10 - 30
0.10 - 20
0.10 - 20
0.10 - 30
240
240
277
120
50 / 60
50 / 60
50 / 60
50 / 60
1
1
1
1
1Pole
2 Pole
1Pole
---
5,000
10,000
10,000
DUAL COIL
Notes from Table D:
1
Special catalog number required. Consult factory.
Table E: Lists UL Recognized, CSA Accepted configurations and performance capabilities as Protectors, Supplementary for
Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classified Small Craft
Electrical Devices, Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors.
Table F: Lists UL Listed configurations and performance capabilities as Circuit Breakers for use in Communications Equipment
(Guide DITT, File E189195), under UL489A.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
C-Series – General Specifications
5
Electrical
Mechanical
Maximum Voltage
AC, 480 WYE/277 VAC, 50/60 Hz
(see Table A.)
UL489: AC,240 VAC. (See Table D),
50/60 Hz, 125 VDC
Standard current coils: 0.100,
0.250, 0.500, 0.750, 1.00, 2.50,
5.00, 7.50, 10.0, 15.0, 25.0, 30.0,
35.0, 40.0, 50.0, 60.0, 70.0, 80.0,
90.0 and 100 amps. Other ratings
available, see Ordering Scheme.
Endurance
10,000 ON-OFF operations @ 6 per
minute; with rated current &
voltage.
Trip Free
All C-Series circuit breakers will trip
on overload, even when actuator is
forcibly held in the ON position.
The operating actuator moves
positively to the OFF position when
an overload causes the breaker to
trip. With mid-trip, handle moves to
the mid position on electrical trip of
the circuit breaker. With mid trip
handle with alarm switch, handle
moves to the mid position and the
alarm switch actuates when the
circuit breaker is electrically
tripped.
Current Rating
Trip Indication
Standard Voltage Coils DC - 6V, 12V; AC - 120V; other
ratings available, see Ordering
Scheme.
Auxiliary Switch Rating SPDT; 10.1 amps-250VAC, DC Aux.
Switch 1.0A, 65 VDC. 0.5A,
80VDC,1/4 HP, 125VAC,VDE & TUV
1.0 125 VAC.
Insulation Resistance
Dielectric Strength
Minimum of 100 Megohms at 500
VDC.
Physical
UL, CSA: 1960 V 50/60 Hz for one
minute between all electrically
isolated terminals. C-Series Circuit
Breakers comply with the 8mm
spacing and 3750V 50/60 Hz
dielectric requirements from
hazardous voltage to operator
accessible surfaces, between
adjacent poles and from main
circuits to auxiliary circuits per
Publications EN 60950 and
VDE 0805.
Number of Poles
1-6 poles ≤ 50A; 1-4 poles @ 51-
70A; 1-2 poles 71-100A. UL489
Handle: 1 pole ≤ 100A, 2 pole ≤
50A; Rocker: 1 pole ≤ 100A.
Internal Circuit Config. Series (with or without auxiliary
switch, mid trip & mid trip with
alarm switch) Shunt & Relay with
current or voltage trip coils, Dual
Coil, Switch Only (with or without
aux. switch). UL489: Series (with or
without auxiliary switch, mid-trip &
midtrip with alarm switch).
Resistance, Impedance Values from Line to Load Terminal -
based on Series Trip Circuit
Weight
Standard Colors
Approx.112 grams/pole ( 3.95 oz).
Housing: Black
RESISTANCE, IMPEDANCE VALUES
Breaker.
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
Environmental
1000
CURRENT
(AMPS)
TOLERANCE
(%)
Designed and tested in accordance with requirements of
specification MIL-PRF-55629 & MIL-STD-202 as follows:
100
10
0.10 - 5.0
5.1 - 20.0
15%
25%
35%
Shock
Withstands 100 Gs, 6ms sawtooth
while carrying rated current per
Method 213, Test Condition “I”.
Instantaneous and ultrashort curves
tested @ 90% of rated current.
Withstands 0.060” excursion from
10-55 Hz & 10 Gs 55-500 Hz, @
rated current per Method 204C,
Test Cond. A. Instantaneous &
ultrashort curves tested @ 90% of
rated current.
Method 106D, i.e., ten 24-hour
cycles @ +25°C to +65°C,
80-98% RH.
Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Method 107D, Condition A (five
cycles @ -55°C to +25°C to +85°C
to +25°C).
O
H
M
S
20.1 - 100.0
1
0.1
0.01
Vibration
0.001
0.01
0.1
1
10
100
AMPERE RATING
Pulse Tolerance Curves
60 Hz 1/2 Cycle
Inrush Pulse Tolerance
50 Hz 1/2 Cycle
Moisture Resistance
Inrush Pulse Tolerance
I
I
r
r
Time Delay Curves
Time Delay Curves
42, 44
& 46
22x
10x
42, 44
& 46
(50 Amps Max.)
(50 Amps Max.)
25x
12x
Time Delay Curves
Time Delay Curves
22, 24 (100 Amps Max.)
26 (70 Amps Max.)
22, 24 (100 Amps Max.)
26 (70 Amps Max.)
Salt Spray
t
t
10.0
20.0
5.0
8.33
16.67
4.165
Time in
Milliseconds
Thermal Shock
Operating Temperature -40°C to +85°C
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
6
C-Series - Agency Certifications
Agency Certifications:
UL Recognized
UL Standard 1077
Component Recognition Program
as Protectors, Supplementary
(Guide CCN/QVNU2, File E75596)
UL Standard 508
UL Standard 1500
Motor Controllers, Manual
(Guide CCN/NLRV2, File E135367)
Protectors, Supplementary for
Marine Electrical & Fuel Systems
(Guide PEQZ2, File E75596)
Ignition Protection
UL Listed
UL Standard 489
Circuit Breakers, Molded Case,
(Guide DIVQ, File E129899)
UL Standard 489A
Communications Equipment
(Guide CCN/DITT, File E189195)
CSA Accepted
Component Supplementary Protector
under Class 3215 30,
File 047848 0 000
CSA Standard C22.2 No. 235
CSA Certified
Circuit Breaker Model Case
(Class 1432 01, File 093910),
CSA Standard C22.2 No. 5.1 - M
TUV Certified
VDE Certified
EN60934, under License No.
R72041016
EN60934, VDE 0642 under File No.
10537
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
C-Series Handle UL Recognized – Ordering Scheme
7
C A 3 B 0 10 450 1 2 1 C
8
9
10
11
Agency
Approval
1
2
3
4
5
6
7
Terminal
Actuator
Color
Mounting
Bezel/Barrier
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
7 CURRENT RATING (AMPERES)
1 SERIES
C
CODE AMPERES
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
2 ACTUATOR1
A
B
S
T
Handle, one per pole
Handle, one per multipole unit
Mid-Trip Handle, one per pole
Mid-Trip, one per pole & Alarm Switch
3 POLES2
1
2
One
Two
3
4
Three
Four
5
6
Five
Six
9
660 60.000
4 CIRCUIT3
F
Relay Trip (current)
Relay Trip (voltage)
Dual Coil with Shunt Trip
Voltage Coil
Dual Coil with Relay Trip
Voltage Coil
9
4
670 70.000
3
4
4,5
A
B
C
D
Switch Only (no coil)
G
H
9
680 80.000
Series Trip (current)
Series Trip (voltage)
Shunt Trip (current)
Shunt Trip (voltage)
9
685 85.000
9
690 90.000
4
4
4,5
K
9
695 95.000
E
9
810 100.000
VOLTAGE COIL (NOMINAL RATED VOLTAGE)7
5 AUXILIARY/ALARM SWITCH
CODE
RATING
0
2
3
4
without Aux Switch
A06 6DC
A12 12DC
A18 18DC
A24 24DC
A32 32DC
A48 48DC
A65 65DC
J06 6AC
J12 12AC
J18 18AC
J24 24AC
J48 48AC
J65 65AC
K20 120AC
L40 240AC
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
6 FREQUENCY & DELAY
8 TERMINAL15
3
10
12
13,15
15
03
10
11
12
14
16
20
21
22
24
26
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
30
31
32
34
36
42
44
46
52
54
56
DC 50/60Hz Instantaneous
DC 50/60Hz Ultra Short
DC 50/60Hz Short
DC 50/60Hz Medium
DC 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
1
2
3
4
5
Stud 10-32
6
7
9
Stud M6
7
11
12
11
11
Screw 10-32
Stud 1/4-20
Stud M5 x 0.8
0.250 Double Click Connect
7/16” Clip Terminal
Plug-In Stud
14
11,15
A
C
Screw M5 x 0.8
5/16” Clip Terminal
8
8
8
8
7
9 ACTUATOR COLOR & LEGEND16
Actuator Color
White
Black
Red
Green
Blue
Yellow
Gray
I-O
A
C
F
H
K
M
P
ON-OFF
Dual
Legend Color
Black
White
White
White
White
Black
Black
Black
8
B
D
G
J
1
2
3
4
5
6
7
8
9
Notes:
L
1
Actuator Code:
N
Q
S
U
A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units.
B: Handle location as viewed from front of breaker:
Orange
Black (short handle)
R
T
2 pole - left pole 3 pole - center pole 4 pole - two handles at center poles
17
5 pole - three handles at center poles
6 pole - four handles at center poles
White
S: Handle moves to mid-position only upon electrical trip of the breaker. Available
with circuit codes B, C, D, E, F, G, H and K.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip
of the breaker. Available with circuit codes B & C.
10 MOUNTING/BARRIERS
MOUNTING STYLE
BARRIERS
VOLTAGE
2
Standard multipole units have all poles identical except when specifying auxiliary
switch and/or mixed poles. 4 pole max w/VDE. 5th pole available as Series Trip w/
Voltage Coil only.
Threaded Insert
1
6-32 x 0.195 inches
6-32 X 0.195 inches
6-32ꢀXꢀ0.195ꢀinchesꢀꢀ
ISO M3 x 5mm
ISO M3 x 5mm
ISOꢀM3ꢀxꢀ5mmꢀꢀ
no
< 300
< 300
≥ꢀ300
< 300
< 300
≥ꢀ300
A
C
2
B
D
yes
yesꢀꢀ
no
yes
yesꢀꢀ
3
ꢀ
Switch Only circuits, rated up to 50 amps and 6 poles, and only available with VDE
Certificationꢀwhenꢀtiedꢀtoꢀaꢀprotectedꢀpoleꢀ(CircuitꢀCodeꢀB,ꢀC,ꢀDꢀorꢀH.).ꢀForꢀ.02ꢀtoꢀꢀ
30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650.
For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit
Codes D, F, H & K available up to 50 amps maximum Current Rating.
Consult factory for available Dual Coil options, as special catalog number is
required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously
on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip
instantaneously and are rated for intermittent duty only.
Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole
breakers, one aux. switch is supplied, mounted in the extreme right pole.
Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20.
Available with Circuit Codes B & D only, and up to 50 amps maximum.
Current Ratings 60 - 70 are available up to four poles maximum. Ratings 71 - 100
are available up to two poles maximum.
18
ꢀ
ꢀ
4
5
18
Front panel Snap-In, 1.00” [25.4mm] wide bezel
17
E
with Handleguard
no
< 300
6
11 AGENCY APPROVAL
C
Dꢀ
Eꢀ
Hꢀ
I
UL Recognized, CSA Accepted
VDEꢀCertified,ꢀULꢀRecognized,ꢀCSAꢀAccepted
TUVꢀCertified,ꢀULꢀRecognized,ꢀCSAꢀAccepted
UL489ꢀConstruction:ꢀVDEꢀCertified,ꢀULꢀRecognized,ꢀCSAꢀꢀAccepted
UL Rec. STD 1077, UL Rec. 1500 (ignition protected), CSA Accepted
UL489 Construction: UL Recognized, CSA Accepted
7
8
9
10 Terminal Code 1 available to 60 amps maximum.
11 Terminal Codes 2, 4, 5 and C available to 50 amps maximum.
12 Terminal Codes 3, 6 & 9 available to 100 amps maximum.
13 Terminal Code 7 available to 25 amps maximum.
14 Terminal Code A available to 100 amps maximum.
15 Terminal Codes 7, 9 & C are not VDE approved.
16 No marking available. Consult factory. VDE/TUV Approval requires dual
(I-O, ON-OFF) or I-O markings on all handles.
L
Rꢀ
UL489ꢀConstruction:ꢀTUVꢀCertified,ꢀULꢀRecognized,ꢀCSAꢀAccepted
17 Single pole only.
18 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 - 4 poles only
and limited to AC Delays. “General Purpose amps” not rated for “full load amps” or
to be used in applications with a motor.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
8
C-Series Handle UL489A Listed / Parallel Pole – Ordering Scheme
C A 2 P 0 D4 820 3 2 1 M T
8
9
10
Mounting
11
12
1
2
3
4
5
6
7
Terminal
Actuator
Color
Max. App. Agency
Rating
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
Approval
8 TERMINAL6
1 SERIES
3
6
A
Stud 1/4-20
Stud M6
C
Plug-In Stud
2 ACTUATOR1
A
S
T
Handle, one per pole
Mid-Trip Handle, one per pole
Mid-Trip, one per pole & Alarm Switch
9 ACTUATOR COLOR2
LEGEND
ON-OFF
Dual
Legend Color
Black
White
White
White
White
Black
Black
Black
White
Black
Red
Green
Blue
Yellow
Gray
Orange
B
D
G
J
1
2
3
4
5
6
7
8
3 POLES4
1
One
2
Two
3
Three
L
4 CIRCUIT5
N
Q
S
B
Series Trip
P
Series Trip (parallel pole)
5 AUXILIARY/ALARM SWITCH
0
2
3
4
without Aux Switch
10 MOUNTING
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
Threaded Insert
1
2
6-32 x 0.195 inches
ISO M3 x 5mm
11 MAXIMUM APPLICATION RATING
80 DC
6 FREQUENCY & DELAY7
M
D1
D2
D4
D6
DC Ultra Short
DC Short
11
12
14
16
DC Ultra Short
DC Short
DC Medium
DC Long
DC Medium
DC Long
12 AGENCY APPROVAL8
A
Without Approval
Jꢀ
T
Kꢀꢀ
7ꢀ
UL489AꢀListed,ꢀTUVꢀCertified
UL489A Listed
UL489AꢀListed,ꢀVDEꢀCertifiedꢀ(upꢀtoꢀ200ꢀamps)
UL489AꢀListed,ꢀTUVꢀCertifiedꢀ(upꢀtoꢀ250ꢀamps)
7 CURRENT RATING (AMPERES)
CODE AMPERES
810 100.00
811 110.00
812 120.00
912 125.00
813 130.00
814 140.00
815 150.00
816 160.00
817 170.00
917 175.00
818 180.00
819 190.00
820 200.00
9224 225.00
8254 250.00
Notes:
1
Handle moves to Mid-Position only upon electrical trip of C/B when Actuator S is
specified.ꢀWhenꢀActuatorꢀCodeꢀTꢀisꢀspecified,ꢀhandleꢀmovesꢀtoꢀMidꢀPositionꢀandꢀꢀ
Alarm Switch actuates only upon electrical trip of C/B.
ꢀ
2
3
Standard Handle colors are White, Black, Red & Yellow.
Breakers with Terminal Codes 3 & 6 are supplied with bus bars connecting the Line
and Load Terminals. For Terminal Code A, Line and Load Terminals must be
connected to a copper bus bar having a minimum cross-section of 0.078 square
inches. Terminal code A not available on the single pole unit.
Rating for 101 to 125 amps are available in 1 pole size. Ratings from 110 to 200
amps are available in 2-pole size. For ratings from 225-250 amps, specify 3-pole size.
Circuit code B only available with 1 pole.
4
5
6
7
8
1 pole only available with terminal codes 3 and 6.
Delays 11, 12, 14, and 16 are only available with 1 pole.
Agency code K and 7 not available with 1 pole.
Agency code J only available with 1 pole.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
C-Series Rocker UL489A Listed / Parallel Pole – Ordering Scheme
9
C 1 2 P 0 D4 820 3 1 A M T
8
9
10
Mounting
11
12
1
2
3
4
5
6
7
Terminal
Actuator
Color
Max. App. Agency
Rating
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
Approval
8 TERMINAL4
1 SERIES
C
3
6
A
Stud 1/4-20
Stud M6
Plug-In Stud
2 ACTUATOR
C
D
F
G
J
K
1
2
3
4
5
6
7
8
Curved Rocker, Two Color Visi, Indicate On, Vertical Legend
Curved Rocker, Two Color Visi, Indicate On, Horizontal Legend
Curved Rocker, Two Color Visi, Indicate Off, Vertical Legend
Curved Rocker, Two Color Visi, Indicate Off, Horizontal Legend
Curved Rocker, Single Color, Vertical Legend
Curved Rocker, Single Color, Horizontal Legend
Flat Rocker, Two Color Visi, Vertical Legend
Flat Rocker, Two Color Visi, Horizontal Legend
Flat Rocker, Single Color, Vertical Legend
Flat Rocker, Single Color, Horizontal Legend
Flat Rocker, Push To Reset, Two Color Visi, Vertical Legend
Flat Rocker, Push To Reset, Two Color Visi, Horizontal Legend
Flat Rocker, Push To Reset, Single Color, Vertical Legend
Flat Rocker, Push To Reset, Single Color, Horizontal Legend
9 ACTUATOR COLOR
LEGEND
ON-OFF
B
D
G
J
Dual
Legend Color
Black
White
White
White
White
Black
Black
Black
White
Black
Red
Green
Blue
Yellow
Gray
Orange
1
2
3
4
5
6
7
8
L
N
Q
S
10 MOUNTING
ROCKER / MOUNTING INSERT STYLE
Standard Rocker Bezel - 6-32 Inserts
Standard Rocker Bezel - M3 Inserts
Rocker Guard Bezel - 6-32 Inserts
Rocker Guard Bezel - M3 Inserts
Standard Bezel with recessed Off Side Flat Rocker - 6-32 Inserts
Standard Bezel with recessed Off Side Flat Rocker - M3 Inserts
Push to Reset Bezel - 6-32 Inserts
3 POLES2
A
B
C
D
E
F
1
One
2
Two
3
Three
4 CIRCUIT3
B
Series Trip
P
Series Trip (parallel pole)
G
H
Push to Reset Bezel - M3 Inserts
5 AUXILIARY/ALARM SWITCH
0
2
3
4
without Aux Switch
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
11 MAXIMUM APPLICATION RATING
80 DC
M
12 AGENCY APPROVAL6
A
Jꢀ
T
Without Approval
UL489AꢀListed,ꢀTUVꢀCertified
UL489A Listed
6 FREQUENCY & DELAY5
D1
D2
D4
D6
DC Ultra Short
DC Short
11
12
14
16
DC Ultra Short
DC Short
DC Medium
DC Long
7ꢀ
UL489AꢀListed,ꢀTUVꢀCertified
DC Medium
DC Long
Notes:
1
Breakers with Terminal Codes 3 & 6 are supplied with bus bars connecting the Line
and Load Terminals. For Terminal Code A, Line and Load Terminals must be
connected to a copper bus bar having a minimum cross-section of 0.078 square
inches. Terminal code A not available on the single pole unit.
Ratings for 101 to 125 amps are availabe in 1-pole size. Ratings from 110 to 200
amps are available in 2-pole size. For ratings from 225-250 amps, specify 3-pole
size.
7 CURRENT RATING (AMPERES)2
CODE AMPERES
2
810 100.00
811 110.00
812 120.00
912 125.00
813 130.00
814 140.00
815 150.00
816 160.00
817 170.00
917 175.00
818 180.00
819 190.00
820 200.00
922 225.00
825 250.00
3
4
5
6
Circuit code B only available with 1-pole.
1 pole only available with terminal codes 3 and 6.
Delays 11, 12, 14, and 16 are only available with 1 pole.
Agency code K and 7 not available with 1 pole.
Agency code J only available with 1 pole.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
10
C-Series Handle UL489 Listed – Ordering Scheme
C A 3 B 0 14 450 1 2 1 K G
8
9
10
Mounting/
Barriers
11
12
1
2
3
4
5
6
7
Terminal
Actuator
Color
Max. App. Agency
Rating Approval
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
7 CURRENT RATING (AMPERES)5
1 SERIES
C
CODE AMPERES
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
660 60.000
670 70.000
680 80.000
685 85.000
690 90.000
695 95.000
810 100.000
2 ACTUATOR1
A
B
S
T
Handle, one per pole
Handle, one per multipole unit
Mid-Trip Handle, one per pole
Mid-Trip, one per pole & Alarm Switch
611
711
11.000
11.500
3 POLES2
1
One
2
Two
3
Three
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
4 CIRCUIT
B
Series Trip (current)
5 AUXILIARY/ALARM SWITCH3
0
2
3
4
without Aux Switch
8 TERMINAL6
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
17
28
39
48
58
Stud 10-32
Screw 10-32
Stud 1/4-20
Stud M5 x 0.8
Screw M5 x 0.8
69
Stud M6
7/16” Clip Terminal
Plug-In Stud
99
A10
C8
5/16” Clip Terminal
6 FREQUENCY & DELAY
11
12
14
16
21
22
24
DC Ultra Short
DC Short
DC Medium
26
50/60Hz Long
424
444
464
524
544
564
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
9 ACTUATOR COLOR & LEGEND11
Actuator Color
White
Black
Red
Green
Blue
Yellow
Gray
ON-OFF
Dual
Legend Color
Black
White
White
White
White
Black
Black
Black
DC Long
B
D
G
J
1
2
3
4
5
6
7
8
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
L
Notes:
N
Q
S
1
Actuator Code:
A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units.
B: Handle located, as viewed from front of breaker in left pole. 2 pole maximum.
S: Handle moves to mid-position only upon electrical trip of the breaker.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip
of the breaker.
Orange
10 MOUNTING/BARRIERS
MOUNTING STYLE
2
ꢀ
Standard multipole units have all poles identical except when specifying auxiliary
switch and/or mixed poles.
12
BARRIERS
Threaded Insert
6-32 x 0.195 inches
ISO M3 x 5mm
2 & 3 pole circuit breakers required for 120/240 VAC (Maximum application rating
code C) applications, have all poles identical except when specifying auxiliary /
alarmꢀswitchꢀwhichꢀisꢀnormallyꢀsuppliedꢀinꢀextremeꢀrightꢀpoleꢀperꢀfigureꢀB.ꢀTerminalꢀꢀ
barriers are required on all multipole breakers.
1
2
yes
yes
Third pole is for 120/240 VAC applications requiring neutral disconnect. The 3rd
pole has the same construction as poles 1 & 2.
11 MAXIMUM APPLICATION RATING
3
On multi-pole breakers, one auxiliary. switch is supplied, mounted in the extreme
right pole.
A
B
C
D
K
F
65 DC
125 DC
120/240 AC
240 AC
120 AC
277 AC
80 DC
VDE approval on auxiliary switch codes 2, 3 & 4 only.
2
Auxiliary / Alarm Switch with Independent Circuit ie: separate from breaker circuit,
only available with circuit breakers rated 50 amp maximum at 80 VDC, 125 VDC,
and 120 VAC. Auxiliary / Alarm Switch with Dependent Circuit ie: same as circuit
breaker, is supplied from factory with common terminal of auxiliary / alarm switch
connected to line terminal on 120/240 and 240 VAC ratings. Circuit breakers rated
120 VAC 50 amp maximum can be supplied with Auxiliary/Alarm switch common
terminal connected to breaker line terminal. Consult factory for special catalog
number.
M
12 AGENCY APPROVAL11
4
5
Available up to 50 amps maximum.
A
w/o approvals
UL489ꢀListed,ꢀCSAꢀCertifiedꢀ&ꢀVDEꢀCertified
ꢀUL489ꢀListedꢀ&ꢀCSAꢀCertified
Current ratings 71 - 100 with VDE approvals are available up to two poles
maximum.
Fꢀꢀ
Gꢀ
Jꢀꢀ
6
7
8
9
Terminal Codes 9 & C are not VDE approved.
Terminal Code 1 available to 60 amps maximum.
UL489ꢀListed,ꢀCSAꢀCertifiedꢀ&ꢀTUVꢀCertified
Terminal Codes 2, 4, 5 & C available to 50 amps maximum.
Terminal Codes 3, 6 & 9 available to 100 amps maximum.
10 Terminal Code A available to 100 amps maximum.
11 VDE and TUV approvals require Dual (I-O, ON-OFF) markings on all handles.
12 Barriers supplied on multi-pole units only.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
C-Series Sealed Toggle UL Recognized – Ordering Scheme
11
C M 3 B 0 10 450 1 0 1 C
8
9
10
11
Agency
Approval
1
2
3
4
5
6
7
Terminal
Legend
Plate
Mounting
Bezel/Barrier
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
7 CURRENT RATING (AMPERES)9
1 SERIES
C
CODE
AMPERES
020
025
030
035
040
045
050
055
060
065
070
075
080
085
090
095
210
215
220
225
230
0.020
0.025
0.030
0.035
0.040
0.045
0.050
0.055
0.060
0.065
0.070
0.075
0.080
0.085
0.090
0.095
0.100
0.150
0.200
0.250
0.300
235
240
245
250
255
260
265
270
275
280
285
290
295
410
512
415
517
420
522
425
527
0.350
0.400
0.450
0.500
0.550
0.600
0.650
0.700
0.750
0.800
0.850
0.900
0.950
1.000
1.250
1.500
1.750
2.000
2.250
2.500
2.750
430
435
440
445
450
455
460
465
470
475
480
485
490
495
610
710
611
711
612
712
613
3.000
3.500
4.000
4.500
5.000
5.500
6.000
6.500
7.000
7.500
8.000
8.500
9.000
9.500
10.000
10.500
11.000
11.500
12.000
12.500
13.000
614
14.000
15.000
16.000
17.000
18.000
20.000
22.000
24.000
25.000
30.000
35.000
40.000
50.000
60.000
70.000
80.000
85.000
90.000
95.000
100.000
615
616
617
618
620
622
624
625
630
635
640
650
660
670
680
685
690
695
810
2 ACTUATOR1
M
Sealed Toggle, one per pole
3 POLES
1
One
2
Two
3
Three
4 CIRCUIT
F3
Relay Trip (current)
Relay Trip (voltage)
Dual Coil with Shunt Trip
Voltage Coil
Dual Coil with Relay Trip
Voltage Coil
2
3
A
B
C
D
Switch Only (no coil)
G
H
3,4
Series Trip (current)
Series Trip (voltage)
Shunt Trip (current)
Shunt Trip (voltage)
9
9
9
9
9
9
9
3
3
3,4
K
E
5 AUXILIARY/ALARM SWITCH
0
2
3
4
without Aux Switch
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
VOLTAGE COIL (NOMINAL RATED VOLTAGE)7
CODE
RATING
A06 6DC
A12 12DC
A18 18DC
A24 24DC
A32 32DC
A48 48DC
A65 65DC
J12 12AC
J18 18AC
J24 24AC
J48 48AC
J65 65AC
K20 120AC
L40 240AC
6 FREQUENCY & DELAY
J06
6AC
032
106
11
12
14
16
206
21
22
24
26
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
30
31
32
34
36
42
44
46
52
54
56
DC 50/60Hz Instantaneous
DC 50/60Hz Ultra Short
DC 50/60Hz Short
DC 50/60Hz Medium
DC 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
8 TERMINAL
19
Stud 10-32
Screw 10-32
Stud 1/4-20
Stud M5 x 0.8
Screw M5 x 0.8
611
712
911
A13
C10
Stud M6
210
311
410
510
0.250 Double Click Connect
7/16” Clip Terminal
Plug-In Stud
7
7
7
7
5/16” Clip Terminal
7
9 LEGENDPLATE
0
No Legend
Notes:
1
Actuator Code M: Handle location as viewed from front of breaker:
2 pole - right pole 3 pole - center pole
10 MOUNTING/BARRIERS
MOUNTING STYLE
1
2
Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE.
For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current
Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select
Current Code 810.
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only.
Consult factory for available Dual Coil options, as special catalog number is
required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously
on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip
instantaneously and are rated for intermittent duty only.
BARRIERS
no
Standard Hex Nut (multi-pole units only) yes
Standard Hex Nut
A
3
4
11 AGENCY APPROVAL
C
L
T
UL Recognized & CSA Accepted
UL Recognized & CSA Accepted with listed construction
UL Recognized & CSA Accepted, UL1500 ignition protection
5
Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole
breakers, one aux. switch is supplied, mounted in the extreme right pole.
Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20.
Available with Circuit Codes B & D only, and up to 50 amps maximum.
Consult factory for current ratings 71-100, in three pole units, available as special
catalog number only.
6
7
8
9
Terminal Code 1 available to 60 amps maximum.
10 Terminal Codes 2, 4, 5 and C available to 50 amps maximum.
11 Terminal Codes 3, 6 & 9 available to 100 amps maximum.
12 Terminal Code 7 available to 25 amps maximum.
13 Terminal Code A available to 100 amps maximum.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
12
C-Series Rocker UL Recognized – Ordering Scheme
14 450
C C 3 B 0
1 2 1 D
6
7
8
9
10
Mounting/
Barriers
11
Agency
Approval
1
2
3
4
5
Frequency
& Delay
Current Rating
Terminal
Actuator
Color
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
1 SERIES
C
7 CURRENT RATING (AMPERES)
CODE AMPERES
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
2 ACTUATOR1
Single color
Two Color Visi-Rocker
J
Vertical legend
C
D
E
F
G
H
Indicate ON, vertical legend
Indicate ON, horizontal legend
Indicate ON, no legend
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
Indicate OFF, no legend
K
L
Horizontal legend
No legend
Push-To-Reset, Single color
R
U
V
Vertical legend
Horizontal legend
No legend
Push-To-Reset, Visi-Rocker
N
O
P
Indicate OFF,
vertical legend
Indicate OFF,
horizontal legend
Indicate OFF,
no legend
9
660 60.000
9
670 70.000
9
680 80.000
9
611
711
11.000
11.500
685 85.000
9
690 90.000
9
612 12.000
712 12.500
613 13.000
695 95.000
9
810 100.000
VOLTAGE COIL (NOMINAL RATED VOLTAGE)7
CODE
RATING
A06 6DC
A12 12DC
A18 18DC
A24 24DC
A32 32DC
A48 48DC
A65 65DC
J06 6AC
J12 12AC
J18 18AC
J24 24AC
J48 48AC
J65 65AC
K20 120AC
L40 240AC
3 POLES2
1
One
2
Two
3
Three
4 CIRCUIT
F4
Relay Trip (Current)
Relay Trip (Voltage)
Dual Coil with Shunt Trip
Voltage Coil
Dual Coil with Relay Trip
Voltage Coil
A3
B
Switch Only (No Coil)
G4
H4,5
8 TERMINAL
10
12
13
Series Trip (Current)
Series Trip (Voltage)
Shunt Trip (Current)
Shunt Trip (Voltage)
1
2
3
4
5
Stud 10-32
6
7
9
Stud M6
11
12
11
11
C
Screw 10-32
Stud 1/4-20
Stud M5 x 0.8
Screw M5 x 0.8
0.250 Double Quick Connect
7/16” Clip Terminal
Plug-In Stud
D4
E4
K4,5
14
A
C
5/16” Clip Terminal
5 AUXILIARY/ALARM SWITCH6
0
2
3
4
without Aux Switch
9 ACTUATOR COLOR & LEGEND16,17,18
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
Actuator or
Visi-Color
Marking:
Marking Color:
Single Color
Rocker/Handle
Black
Color:
White
Black
Red
I-O
A
C
F
ON-OFF
Dual/None
Visi-Rocker
White
n/a
B
D
G
J
1
2
3
4
5
6
7
8
White
6 FREQUENCY & DELAY
White
Red
03
107
11
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
30
DC 50/60Hz Instantaneous
DC 50/60Hz Ultra Short
DC 50/60Hz Short
DC 50/60Hz Medium
DC 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
Green
Blue
H
K
M
P
White
Green
Blue
31
L
White
32
Yellow
Gray
Orange
N
Q
S
Black
Yellow
Gray
12
14
16
207
21
22
24
26
34
Black
36
R
Black
Orange
428
448
468
528
548
568
10 MOUNTING/BARRIERS1
STANDARD ROCKER BEZEL
BARRIERS
no
VOLTAGE
<300
1
2
3
4
5
6
6-32 x 0.195 inches
6-32 x 0.195 inches
ꢀꢀ 6-32ꢀxꢀ0.195ꢀinchesꢀ
ISO M3 x 5mm
yes
<300
19
19
yesꢀ
no
≥300
Notes:
<300
1
2
Push-To-Reset actuators have OFF portion of rocker shrouded.
ISO M3 x 5mm
yes
<300
Multi-pole breakers have all poles identical except when specifying Aux. switch and/
or mixed poles, and have one rocker per breaker. Rocker location as viewed from
front panel: 2 pole – left pole; 3 pole – center pole.
ꢀꢀ ISOꢀM3ꢀxꢀ5mmꢀ
ROCKERGUARD BEZEL
6-32 x 0.195 inches
6-32 x 0.195 inches
yesꢀ
≥300
3
ꢀ
Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE
Certificationꢀwhenꢀtiedꢀtoꢀaꢀprotectedꢀpoleꢀ(CircuitꢀCodeꢀB,ꢀC,ꢀDꢀorꢀH.),ꢀForꢀ.02ꢀtoꢀꢀ
30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650.
For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit
Codes D,F,H & K available up to 50 amps maximum Current Rating.
Consult factory for available Dual Coil options, as special catalog number is
required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously
on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip
instantaneously and are rated for intermittent duty only.
A
C
E
G
J
no
<300
<300
≥300
<300
<300
≥300
yes
yesꢀ
no
19
ꢀꢀ 6-32ꢀxꢀ0.195ꢀinchesꢀ
ISO M3 x 5mm
4
5
ISO M3 x 5mm
yes
yesꢀ
19
L
ꢀꢀ ISOꢀM3ꢀxꢀ5mmꢀ
PUSH-TO-RESET BEZEL
6-32 x 0.195 inches
6-32 x 0.195 inches
ꢀꢀ 6-32ꢀxꢀ0.195ꢀinchesꢀ
ISO M3 x 5mm
B
D
no
<300
<300
≥300
<300
<300
≥300
yes
yesꢀ
no
19
F
6
Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole
breakers, one aux. switch is supplied, mounted in the extreme right pole. Auxiliary
switch codes 2, 3 & 4 are VDE approved.
H
J
ISO M3 x 5mm
ꢀꢀ ISOꢀM3ꢀxꢀ5mmꢀ
yes
yesꢀ
19
7
8
9
Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20.
Available with Circuit Codes B & D only, and up to 50 amps maximum.
Current Ratings 60-70 are available up to four poles maximum. Ratings 71-100 are
available up to two poles maximum.
M
10 Terminal Code 1 available to 60 amps maximum.
11 AGENCY APPROVAL
11 Terminal Codes 2,4,5 & C available to 50 amps maximum.
12 Terminal Codes 3,6 & 9 available to 100 amps maximum.
13 Terminal Code 7 available to 25 amps maximum.
C
UL Recognized & CSA Accepted
VDEꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted
TUVꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted
UL489ꢀConstruction:ꢀVDEꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted
UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted
UL489 Construction: UL Recognized & CSA Accepted
Dꢀꢀ
Eꢀꢀ
Hꢀꢀ
I
14 Terminal Code A available to 100 amps maximum.
15 Terminal Codes 7, 9 & C are not VDE approved.
16 Color shown is visi and legend with remainder of rocker black
17 Legend on Push-to-reset bezel/shroud is white when single color rocker is ordered.
Dual = ON-OFF/I-O legend with actuator codes C - G, and J, K, N, O, R, & U. None
= no legend with actuator codes H, L, P, V. Rockerguard available with actuator
codes C - L. Push-to-reset available with actuator codes N, O, P, R, U, V.
18 VDE/TUV approval requires Dual (I-O, ON-OFF) or I-O markings on rocker.
19 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 - 4 poles only
and limited to AC Delays. “General Purpose amps” not rated for “full load amps” or
to be used in applications with a motor.
L
Rꢀ
UL489ꢀConstruction:ꢀTUVꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
C-Series Rocker UL Listed – Ordering Scheme
13
C C 3 B 0 14 450 1 2 A K G
8
9
10
Mounting/
Barriers
11
12
1
2
3
4
5
6
7
Terminal
Actuator
Color
Max. App. Agency
Rating
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
Approval
7 CURRENT RATING (AMPERES)4
1 SERIES
C
CODE AMPERES
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
660 60.000
670 70.000
680 80.000
685 85.000
690 90.000
695 95.000
810 100.000
2 ACTUATOR1
Two Color Visi-Rocker
C
D
F
Indicate ON, vertical legend
Single color
Indicate ON, horizontal legend
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
J
K
Vertical legend
Horizontal legend
G
ROCKER STYLE DESCRIPTIONS
INDICATE "ON"
INDICATE "OFF"
SINGLE COLOR
CODE "C"
CODE "F"
CODE "J"
CODE "K"
LINE
INDICATE
COLOR
LINE
LINE
LOCATION
CODE "D"
CODE "G"
LINE
LINE
LINE
8 TERMINAL
5
7
1
2
Stud 10-32
6
9
Stud M6
7/16” Clip Terminal
Plug-In Stud
6
7,8
7,8
Screw 10-32 w/saddle &
3 POLES1
washer clamps
Stud 1/4-20
Stud M5 x 0.8
Screw M5 x 0.8 w/saddle &
washer clamps
A
C
7
6
6
6,8
1
One
2
Two
3
Three
3
4
5
5/16” Clip Terminal
4 CIRCUIT
B
Series Trip (current)
9 ACTUATOR COLOR & LEGEND11
5 AUXILIARY/ALARM SWITCH2
Actuator or
0
2
3
4
without Aux Switch
Visi-Color
Marking:
Marking Color:
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
Single Color
10
Color:
White
Black
Red
ON-OFF
Dual
Rocker/Handle
Visi-Rocker
White
n/a
B
D
G
J
1
2
3
4
5
6
7
8
Black
White
White
Red
Green
Blue
White
Green
Blue
L
White
6 FREQUENCY & DELAY
26
42
44
46
52
54
56
50/60Hz Long
8
8
8
8
8
Yellow
Gray
Orange
N
Q
S
Black
Yellow
Gray
11
12
14
16
21
22
24
DC Ultra Short
DC Short
DC Medium
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
Black
Black
Orange
DC Long
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
10 MOUNTING/BARRIERS12
13
Standard Rocker Bezel
Threaded Insert, 2 per pole
6-32 X 0.195 inches
BARRIERS
A
C
yes
yes
Notes:
ISO M3 x 5mm
1
Multi-pole breakers have all breakers identical except when specifying Aux. switch
and/or mixed poles, and have one rocker per breaker.
On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right
pole.
Available up to 50 amps maximum.
Current ratings 71 - 100 with VDE approvals are available up to two poles maximum.
Terminal Code 1 available to 60 amps maximum.
Rockerguard Bezel
Threaded Insert, 2 per pole
6-32 x 0.195 inches
2
B
D
yes
yes
ISO M3 x 5mm
3
4
5
6
7
8
9
Terminal Codes 2, 4, 5 & C available to 50 amps maximum.
Terminal Codes 3, 6, 9 & A available to 100 amps maximum.
Terminal Codes 9 & C are not VDE approved.
11 MAXIMUM APPLICATION RATING
A
B
C
D
F
K
M
65 DC
125 DC
120/240 AC
240 AC
277 AC
120 AC
80 DC
Color shown is visi and legend with remainder of rocker black
14
10 Dual = ON-OFF/I-O legend on actuator.
11 VDE and TUV approval requires Dual (I-O, ON-OFF) markings on rocker.
12 Rockerguard available with all actuator codes.
13 Barriers supplied on multi-pole units only.
14 2 & 3 pole circuit breakers required for 120/240 AC rating.
12 AGENCY APPROVAL
A
Fꢀꢀ
G
without approvals
ULꢀ489ꢀListed,ꢀCSAꢀCertified,ꢀ&ꢀVDEꢀCertified
ULꢀ489ꢀListedꢀ&ꢀCSAꢀCertified
Jꢀꢀ
UL489ꢀListed,ꢀCSAꢀCertifiedꢀ&ꢀTUVꢀCertified
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
14
C-Series Flat Rocker UL Recognized – Ordering Scheme
C 1 2 B 0 10 450 1 2 1 E
8
9
10
Mounting/
Barriers
11
Agency
Approval
1
2
3
4
5
6
7
Terminal
Actuator
Color
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
1 SERIES
C
7 CURRENT RATING (AMPERES)9
CODE AMPERES
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
2 ACTUATOR1
Two Color Visi-Rocker
1
2
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
Single color
3
4
Vertical legend
Horizontal legend
Push-To-Reset, Visi-Rocker
5
6
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
9
660 60.000
Push-To-Reset , Single color
9
670 70.000
7
8
Vertical legend
Horizontal legend
9
680 80.000
9
611
711
11.000
11.500
685 85.000
9
690 90.000
9
612 12.000
712 12.500
613 13.000
695 95.000
9
3 POLES2
810 100.000
1
One
2
Two
3
Three
VOLTAGE COIL (NOMINAL RATED VOLTAGE)7
CODE
RATING
4
A06 6DC
A12 12DC
A18 18DC
A24 24DC
A32 32DC
A48 48DC
A65 65DC
J12 12AC
J18 18AC
J24 24AC
J48 48AC
J65 65AC
K20 120AC
L40 240AC
4 CIRCUIT
F
Relay Trip (Current)
Relay Trip (Voltage)
Dual Coil with Shunt Trip
Voltage Coil
Dual Coil with Relay Trip
Voltage Coil
3
4
4,5
A
B
C
D
Switch Only (No Coil)
G
H
Series Trip (Current)
Series Trip (Voltage)
Shunt Trip (Current)
Shunt Trip (Voltage)
J06
6AC
4
4
4,5
K
E
8 TERMINAL
10
12
1
2
3
4
5
Stud 10-32
6
7
9
Stud M6
11
12
11
11
13
15
14
Screw 10-32
Stud 1/4-20
0.250 Double Quick Connect
7/16” Clip Terminal
Plug-In Stud
5 AUXILIARY/ALARM SWITCH6
0
2
3
4
without Aux Switch
Stud M5 x 0.8
Screw M5 x 0.8
A
C
15
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
5/16” Clip Terminal
9 ACTUATOR COLOR & LEGEND16,17,18
Actuator or
Visi-Color
Marking:
Marking Color:
6 FREQUENCY & DELAY
30
31
32
34
36
42
44
46
52
54
56
DC 50/60Hz Instantaneous
DC 50/60Hz Ultra Short
DC 50/60Hz Short
DC 50/60Hz Medium
DC 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
03
10
11
12
14
16
20
21
22
24
26
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
Single Color
Rocker/Handle
Black
7
Color:
White
Black
Red
I-O
A
C
F
H
K
M
P
ON-OFF
Dual/None
Visi-Rocker
White
n/a
B
D
G
J
1
2
3
4
5
6
7
8
White
8
8
8
8
8
8
White
Red
Green
Blue
White
Green
Blue
L
White
7
Yellow
Gray
N
Q
S
Black
Yellow
Gray
Black
Orange
R
Black
Orange
Notes:
10 MOUNTING/BARRIERS1
STANDARD ROCKER BEZEL
1
2
Push-to-reset actuators have OFF portion of rocker shrouded.
BARRIERS
no
VOLTAGE
<300
Multi-pole breakers have all poles identical except when specifying Aux. switch and/or
mixed poles, and have one rocker per breaker. Rocker location as viewed from front
panel: 2 pole – left pole; 3 pole – center pole.
1
2
3
4
5
6
6-32 x 0.195 inches
6-32 x 0.195 inches
ꢀꢀ 6-32ꢀxꢀ0.195ꢀinchesꢀꢀ
ISO M3 x 5mm
yes
<300
19
yesꢀꢀ
no
≥300
3
Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE
Certificationꢀwhenꢀtiedꢀtoꢀaꢀprotectedꢀpoleꢀ(CircuitꢀCodeꢀB,ꢀC,ꢀDꢀorꢀH.).ꢀForꢀ.02ꢀtoꢀ30ꢀꢀ
amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. For
55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit
Codes D,F,H & K available up to 50 amps maximum Current Rating.
Consult factory for available Dual Coil options, as special catalog number is required.
Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line
voltage. Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously
and are rated for intermittent duty only.
<300
ꢀ
ISO M3 x 5mm
yes
<300
19
ꢀꢀ ISOꢀM3ꢀxꢀ5mmꢀꢀ
RECESSED OFF ROCKER
yesꢀꢀ
≥300
4
5
7
8
6-32 x 0.195 inches
6-32 x 0.195 inches
6-32ꢀxꢀ0.195ꢀinchesꢀꢀ
ISO M3 x 5mm
ISO M3 x 5mm
ISOꢀM3ꢀxꢀ5mmꢀꢀ
no
<300
<300
≥300
<300
<300
≥300
yes
yesꢀꢀ
no
9ꢀꢀ
A
C
yes
yesꢀꢀ
6
Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole
breakers, one aux. switch is supplied, mounted in the extreme right pole. Auxilary
switch codes 2, 3 & 4 are VDE approved.
Eꢀꢀ
PUSH-TO-RESET BEZEL
B
D
6-32 x 0.195 inches
6-32 x 0.195 inches
ꢀꢀ 6-32ꢀxꢀ0.195ꢀinchesꢀꢀ
ISO M3 x 5mm
no
<300
<300
≥300
<300
<300
≥300
7
8
9
Voltage coils not rated for continuous duty. Available only with delay codes 10 and 20.
Available with Circuit Codes B & D only, and up to 50 amps maximum.
Current ratings 60-70 are available up to four poles maximum. Current ratings 71 -
100 are available up to two poles maximum.
yes
yesꢀꢀ
no
19
F
H
J
ISO M3 x 5mm
yes
yesꢀꢀ
10 Terminal Code 1 available to 60 amps maximum.
19
M
ꢀꢀ ISOꢀM3ꢀxꢀ5mmꢀꢀ
11 Terminal Codes 2,4,5 & C available to 50 amps maximum.
12 Terminal Codes 3,6 & 9 available to 100 amps maximum.
13 Terminal Code 7 available to 25 amps maximum.
14 Terminal Code A available to 100 amps maximum.
15 Terminal Codes 7, 9 & C are not VDE approved.
11 AGENCY APPROVAL
C
Eꢀꢀ
I
UL Recognized & CSA Accepted
TUVꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted
UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted
UL489 Construction: UL Recognized & CSA Accepted
16 Color shown is visi & legend with remainder of rocker black. Dual = ON-OFF/I-O
legend.
17 Legend on Push-to-reset bezel/shroud is white with single color actuator codes 7 &
8. Legend on Push-to-reset bezel/shroud matches visi-color of rocker with actuator
codes 5 & 6.
L
Rꢀꢀ
UL489ꢀConstruction:ꢀTUVꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted
18 VDE/TUV approval requires Dual (I-O, ON-OFF) or I-O markings on rocker.
19 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 & 3 poles only and
limited to AC Delays. “General Purpose amps” not rated for “full load amps” or to be
used in applications with a motor.
20 Recessed “OFF SIDE” available with actuator codes 1,2,3&4. Legends on rocker are
available in ink stamping only.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
C-Series Flat Rocker UL Listed – Ordering Scheme
15
C 1 2 B 0 14 450 1 2 A K G
8
9
10
Mounting/
Barriers
11
12
1
2
3
4
5
6
7
Terminal
Actuator
Color
Max. App. Agency
Rating
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
Approval
7 CURRENT RATING (AMPERES)5
1 SERIES
C
CODE AMPERES
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
660 60.000
670 70.000
680 80.000
685 85.000
690 90.000
695 95.000
810 100.000
2 ACTUATOR1
Two Color Visi-Rocker
1
2
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
Single color
3
4
Vertical legend
Horizontal legend
611
711
11.000
11.500
Push-To-Reset, Visi-Rocker
5
6
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
Push-To-Reset , Single color
7
8
Vertical legend
Horizontal legend
3 POLES2
1
One
2
Two
3
Three
8 TERMINAL
7
9
1
2
3
4
5
Stud 10-32
6
9
Stud M6
7/16” Clip Terminal
Plug-In Stud
8
9
8
8
9,10
9
4 CIRCUIT
Screw 10-32
Stud 1/4-20
Stud M5 x 0.8
Screw M5 x 0.8
B
Series Trip (current)
A
C
8,10
5/16” Clip Terminal
5 AUXILIARY/ALARM SWITCH2
0
2
3
4
without Aux Switch
9 ACTUATOR COLOR & LEGEND12
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
Actuator or
Visi-Color
Marking:
Marking Color:
Single Color
Rocker/Handle
Black
White
White
White
White
Black
Black
11
Color:
White
Black
Red
Green
Blue
Yellow
Gray
Orange
ON-OFF
Dual
Visi-Rocker
White
n/a
Red
Green
Blue
Yellow
Gray
Orange
B
D
G
J
1
2
3
4
5
6
7
8
6 FREQUENCY & DELAY
11
12
14
16
21
22
24
DC Ultra Short
DC Short
DC Medium
26
42
44
46
52
54
56
50/60Hz Long
4
4
4
4
4
4
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
L
DC Long
N
Q
S
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
Black
1
2
3
Notes:
10 MOUNTING/BARRIERS12
STANDARD ROCKER BEZEL
Threaded Insert, 2 per pole
Push-to-reset actuators have OFF portion of rocker shrouded.
Multi-pole breakers have all breakers identical except when specifying Aux. switch
and/or mixed poles, and have one rocker per breaker.
On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right
pole.
15
BARRIERS
A
C
6-32 X 0.195 inches
ISO M3 x 5mm
yes
yes
4
14
5
6
7
8
9
Available up to 50 amps maximum.
RECESSED OFF ROCKER
Current ratings 71 - 100 with VDE approvals are available up to two poles maximum.
Terminal Code 1 available to 60 amps maximum.
Threaded Insert, 2 per pole
6-32 x 0.195 inches
ISO M3 x 5mm
E
F
yes
yes
Terminal Codes 2, 4, 5 & C available to 50 amps maximum.
Terminal Codes 3, 6, 9 & A available to 100 amps maximum.
13
PUSH-TO-RESET BEZEL
10 Terminal Codes 9 & C are not VDE approved.
11 Color shown is visi and legend with remainder of rocker black
12 Dual = ON-OFF/I-O legend on actuator.
Threaded Insert, 2 per pole
6-32 x 0.195 inches
ISO M3 x 5mm
B
D
yes
yes
13 VDE and TUV approval requires Dual (I-O, ON-OFF) markings on rocker.
14 Legend on push-to-reset bezel/shroud is white when single color rocker is ordered.
Legend on push-to-reset bezel/shroud matches visi-color of rocker with actuator
codes
11 MAXIMUM APPLICATION RATING
15 5 & 6.
A
B
C
D
F
K
M
65 DC
16 Recessed “OFF-SIDE” available with actuator codes 1, 2, 3, & 4. Legends on rocker
are available in ink stamping only.
125 DC
120/240 AC
240 AC
277 AC
120 AC
80 DC
16
17 Barriers supplied on multi-pole units only.
18 2 & 3 pole circuit breakers required for 120/240 AC rating.
12 AGENCY APPROVAL
A
Gꢀꢀ
Jꢀꢀ
without approvals
ULꢀ489ꢀListedꢀ&ꢀCSAꢀCertified
UL489ꢀListed,ꢀCSAꢀCertifiedꢀ&ꢀTUVꢀCertified
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
16
C-Series Handle – Circuit & Terminal Diagrams
.960 [24.38]
.311 DIA [Ø7.90]
.558 [14.17]
Notes:
1
2
3
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Available on Series Trip and Switch Only Circuits when called for on multi-pole units.
Onlyꢀoneꢀaux.ꢀswitchꢀisꢀnormallyꢀsupplied,ꢀasꢀviewedꢀinꢀmulit-poleꢀidentificationꢀscheme.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
C-Series Handle – Circuit & Terminal Diagrams
17
Notes:
1
2
3
4
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Schematic shown represents current trip circuits.
Available only as special catalog number.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
18
C-Series Handle – Form & Fit Drawings
Notes:
1
2
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
C-Series Handleguard – Form & Fit Drawings
19
Notes:
1
2
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
20
C-Series Arc Chute Barrier UL Recognized/Listed – Form & Fit Drawings
Notes:
1
Onlyꢀ1-poleꢀandꢀ3-poleꢀconfigurationsꢀshown.ꢀArcꢀchuteꢀ(w/oꢀbarrier)ꢀandꢀarcꢀchuteꢀꢀ
barrier also available for 2-pole construction.
2
3
Dimensions apply to all variations shown.
Notice that line and load terminal orientation for indicate on and indicate off rocker
circuit breakers are opposite.
4
ꢀ
5
6
7
Screw type terminals shown for Rocker style (CF1, C11, etc) circuit breakers. For
otherꢀterminalꢀconfigurationsꢀseeꢀcircuitꢀandꢀterminalꢀdiagrams.
All dimensions are in inches [millimeters].
Toleranceꢀ±ꢀ.020ꢀunlessꢀotherwiseꢀspecified.
Must be ordered under a special catalog number.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
C-Series Parallel Pole – Form & Fit Drawings
21
Notes:
1
2
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
22
C-Series Sealed Toggle – Form & Fit Drawings
Notes:
1
2
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
C-Series Rocker – Circuit & Terminal Diagrams
23
Notes:
1
2
3
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Schematic shown represents current trip circuit.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
24
C-Series Rocker – Form & Fit Drawings
Notes:
1
2
3
4
Dimensions apply to all variations shown. Notice that circuit breaker line and load terminal orientation on indicate OFF is opposite of indicate ON.
For pole orientation with horizontal legend, rotate front view clockwise 90°.
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
C-Series Flat Rocker – Form & Fit Drawings
25
Notes:
1
2
3
For pole orientation with horizontal legend, rotate front view clockwise 90°.
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
26
Reps & Contact
Authorized Sales Representatives
Click on the group name on the map below to find your local representative or visit
www.carlingtech.com/findarep.
Matera
W. Canada
Matera
E. Canada
MIDWEST
DM
MichigaNn ORTHERN
TEMCO Northwest
ND
SD
WA
OR
Hanna Lind Ltd.
MT
ME
VT
WI
Sierra
MN
Melody
NH
Emery
MI
LD. Allen MA
ID
Norris
NY
CT
WY
«
IA
IN
DM Assoc
OH East
PA
RI
Bridge Marketing
NE
KS
Pacent
Omega Limited
Dy-tronix Inc.
DM
NJ
NV
IL
TSI North
DE
Assoc
WV
MD
TSI
UT
CO
KY
VA
CA
MO
TN
NC
SC
Luscombe
Signal
OK
Engineering
WEST
Enterprises
AR
Pinnacle Marketing
AZ
NM
Sunbelt Components
MS
AL
GA
TX
SOUTHEAST
LA
Matrix
DM Mexico
South America
Mexico
ProRep
Solutions
FL
LATIN AMERICA
Europe
Middle East
Africa
Asia-Pacific
Oceania
Americas
About Carling
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches
and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power
distribution systems. With four ISO registered manufacturing facilities and technical sales offices worldwide,
Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical
components, they engineer powerful solutions! To learn more about Carling please visit
www.carlingtech.com/company-profile.
To view all of Carling’s environmental, quality, health & safety certifications please visit
www.carlingtech.com/environmental-certifications
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
Notes
27
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Phone: 860.793.9281 Fax: 860.793.9231
@
Email: sales carlingtech.com
@
Northern Region Sales Office: nrsm carlingtech.com
@
Southeast Region Sales Office: sersm carlingtech.com
@
Midwest Region Sales Office: mrsm carlingtech.com
@
West Region Sales Office: wrsm carlingtech.com
@
Latin America Sales Office: larsm carlingtech.com
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacific Ltd.,
Kowloon, Hong Kong
Phone: Int + 852-2737-2277 Fax: Int + 852-2736-9332
@
Email: sales carlingtech.com.hk
@
Shenzhen, China: shenzhen carlingtech.com
@
Shanghai, China: shanghai carlingtech.com
@
Pune, India: india carlingtech.com
@
Kaohsiung, Taiwan: taiwan carlingtech.com
@
Yokohama, Japan: japan carlingtech.com
|
|
Europe Middle East Africa Headquarters
Carling Technologies LTD
4 Airport Business Park, Exeter Airport,
Clyst Honiton, Exeter, Devon, EX5 2UL, UK
Phone: Int + 44 1392.364422 Fax: Int + 44 1392.364477
@
Email: ltd.sales carlingtech.com
@
Germany: gmbh carlingtech.com
@
France: sas carlingtech.com
www.carlingtech.com
REV_08_2015
相关型号:
©2020 ICPDF网 联系我们和版权申明